Power Stations WORLDWIDETHE GLOBAL EDITION 01
ILLUSTRATIVE ENGINEERING CALCULATION

Power-factor correction calculator

Explore the theoretical reactive compensation needed to improve a lagging power factor while keeping active power constant.

Educational reference only. Examples and calculator results are not approved installation designs, equipment selections or operating instructions.

Your inputs

Results update as you edit. Use a decimal point. Default values are hypothetical, not recommended equipment sizes.

Electrical input or load power, not motor shaft output.

Enter a positive power factor up to 1, for example 0.9.

Enter a positive power factor up to 1, for example 0.9.

Illustrative result

Theoretical compensation
138.308 kvar
Initial apparent power
333.333 kVA
Target apparent power
263.158 kVA

Worked steps

  1. tan(φinitial) = tan(acos(0.75)) = 0.882
  2. tan(φtarget) = tan(acos(0.95)) = 0.329
  3. Qc = 250 × (0.882 − 0.329) ≈ 138.308 kvar

Calculations use unrounded values; displayed steps are rounded to three decimal places or five significant digits for extreme values.

Formula and units

Qc (kvar) = P × [tan(acos(PFinitial)) − tan(acos(PFtarget))]

Change one input to see its effect. Inputs are calculated in your browser and are not submitted to a calculation service.