Transformer loading calculator

Compare a load’s apparent power with a transformer’s nameplate kVA rating. This is a loading ratio, not a thermal approval.

Educational reference only. Examples and calculator results are not approved installation designs, equipment selections or operating instructions.

Your inputs

Results update as you edit. Use a decimal point. Default values are hypothetical, not recommended equipment sizes.

Electrical input or load power, not motor shaft output.

Enter a positive power factor up to 1, for example 0.9.

Use apparent-power kVA, not an assumed kW rating.

Illustrative result

Nameplate loading ratio
66.667 %
Load apparent power
666.667 kVA

A ratio at or below 100% does not establish safe loading; cooling, harmonics and manufacturer limits still matter.

Worked steps

  1. Sload = 600 / 0.9 = 666.667 kVA
  2. Loading = 100 × 666.667 / 1,000 ≈ 66.667%

Calculations use unrounded values; displayed steps are rounded to three decimal places or five significant digits for extreme values.

Formula and units

Sload (kVA) = P / PF; loading (%) = 100 × Sload / Srated

Change one input to see its effect. Inputs are calculated in your browser and are not submitted to a calculation service.